D36 Series MOV for Distribution Arrester is an advanced surge protection device designed to protect electrical systems and equipment from damaging transient voltages. It is designed with a superior metal oxide varistor technology that responds quickly and accurately to both low and high frequency transients, providing an extremely efficient form of surge protection. In addition, the series features a special design that allows for easy installation and maintenance. With its superior engineering design and superior performance, the D36 Series MOV for Distribution Arrester is the excellent choice for protecting your electrical system from surges and transients.
Type | D36H18.3 |
Nominal discharge current In kA | 10 |
Suggested rated voltage kV | 2.82 |
Diameter mm | 36±0.7 |
Height mm | 18.3±0.3 |
AVG Gradient V/mm | 235 |
DC U1mA kV | 4.30±0.30 |
Iref mA | 2 |
Uref kV | 3.09 |
Ures kV | 7.78±0.55 |
8/20uS repetitive charge transfer Qrs C | 0.4 |
2ms repetitive charge transfer Qrs C | 0.7 |
2ms duration of rectangular impulse current A | 350 |
4/10µs high current test kA | 100 |
Accelerated ageing test Kct | ≤ 1.0 |
Note:
The nouns, parameters and corresponding test methods in this parameter list conform to the standards of IEC60099-4:2014 and GB11032-2020.
The rated voltage, power frequency reference current and power frequency reference voltage are reference values.
The 2ms square wave tolerance value is based on the declared current/2ms repetitive charge transfer charge Qrs=423, if the actual test waveform 2ms current/2mS repetitive charge transfer charge Qrs is not equal to 423, it should be corrected according to the actual 2ms current waveform and Qrs value.
The charging rate of the aging test was 90%.
The number of pulses for the high current withstand value is two.
Type | D36H20.7 |
Nominal discharge current In kA | 10 |
Suggested rated voltage kV | 3.21 |
Diameter mm | 36±0.7 |
Height mm | 20.7±0.3 |
AVG Gradient V/mm | 235 |
DC U1mA kV | 4.86±0.30 |
Iref mA | 2 |
Uref kV | 3.49 |
Ures kV | 8.8±0.55 |
8/20uS repetitive charge transfer Qrs C | 0.4 |
2ms repetitive charge transfer Qrs C | 0.7 |
2ms duration of rectangular impulse current A | 350 |
4/10µs high current test kA | 100 |
Accelerated ageing test Kct | ≤ 1.0 |
Note:
The nouns, parameters and corresponding test methods in this parameter list conform to the standards of IEC60099-4:2014 and GB11032-2020.
The rated voltage, power frequency reference current and power frequency reference voltage are reference values.
The 2ms square wave tolerance value is based on the declared current/2ms repetitive charge transfer charge Qrs=423, if the actual test waveform 2ms current/2mS repetitive charge transfer charge Qrs is not equal to 423, it should be corrected according to the actual 2ms current waveform and Qrs value.
The charging rate of the aging test was 90%.
The number of pulses for the high current withstand value is two.
Type | D36H27.5 |
Nominal discharge current In kA | 10 |
Suggested rated voltage kV | 4.29 |
Diameter mm | 36±0.7 |
Height mm | 27.5±0.3 |
AVG Gradient V/mm | 235 |
DC U1mA kV | 6.46±0.30 |
Iref mA | 2 |
Uref kV | 4.64 |
Ures kV | 11.7±0.55 |
8/20uS repetitive charge transfer Qrs C | 0.4 |
2ms repetitive charge transfer Qrs C | 0.7 |
2ms duration of rectangular impulse current A | 350 |
4/10µs high current test kA | 100 |
Accelerated ageing test Kct | ≤ 1.0 |
Note:
The nouns, parameters and corresponding test methods in this parameter list conform to the standards of IEC60099-4:2014 and GB11032-2020.
The rated voltage, power frequency reference current and power frequency reference voltage are reference values.
The 2ms square wave tolerance value is based on the declared current/2ms repetitive charge transfer charge Qrs=423, if the actual test waveform 2ms current/2mS repetitive charge transfer charge Qrs is not equal to 423, it should be corrected according to the actual 2ms current waveform and Qrs value.
The charging rate of the aging test was 90%.
The number of pulses for the high current withstand value is two.
Type | D36H30.5 |
Nominal discharge current In kA | 10 |
Suggested rated voltage kV | 4.75 |
Diameter mm | 36±0.7 |
Height mm | 30.5±0.3 |
AVG Gradient V/mm | 235 |
DC U1mA kV | 7.17±0.35 |
Iref mA | 2 |
Uref kV | 5.14 |
Ures kV | 12.97±0.64 |
8/20uS repetitive charge transfer Qrs C | 0.4 |
2ms repetitive charge transfer Qrs C | 0.7 |
2ms duration of rectangular impulse current A | 350 |
4/10µs high current test kA | 100 |
Accelerated ageing test Kct | ≤ 1.0 |
Note:
The nouns, parameters and corresponding test methods in this parameter list conform to the standards of IEC60099-4:2014 and GB11032-2020.
The rated voltage, power frequency reference current and power frequency reference voltage are reference values.
The 2ms square wave tolerance value is based on the declared current/2ms repetitive charge transfer charge Qrs=423, if the actual test waveform 2ms current/2mS repetitive charge transfer charge Qrs is not equal to 423, it should be corrected according to the actual 2ms current waveform and Qrs value.
The charging rate of the aging test was 90%.
The number of pulses for the high current withstand value is two.
Type | D36H31 |
Nominal discharge current In kA | 10 |
Suggested rated voltage kV | 4.83 |
Diameter mm | 36±0.7 |
Height mm | 31±0.3 |
AVG Gradient V/mm | 235 |
DC U1mA kV | 7.29±0.35 |
Iref mA | 2 |
Uref kV | 5.23 |
Ures kV | 13.19±0.64 |
8/20uS repetitive charge transfer Qrs C | 0.4 |
2ms repetitive charge transfer Qrs C | 0.7 |
2ms duration of rectangular impulse current A | 350 |
4/10µs high current test kA | 100 |
Accelerated ageing test Kct | ≤ 1.0 |
Note:
The nouns, parameters and corresponding test methods in this parameter list conform to the standards of IEC60099-4:2014 and GB11032-2020.
The rated voltage, power frequency reference current and power frequency reference voltage are reference values.
The 2ms square wave tolerance value is based on the declared current/2ms repetitive charge transfer charge Qrs=423, if the actual test waveform 2ms current/2mS repetitive charge transfer charge Qrs is not equal to 423, it should be corrected according to the actual 2ms current waveform and Qrs value.
The charging rate of the aging test was 90%.
The number of pulses for the high current withstand value is two.
Type | D36H34.5 |
Nominal discharge current In kA | 10 |
Suggested rated voltage kV | 5.38 |
Diameter mm | 36±0.7 |
Height mm | 34.5±0.3 |
AVG Gradient /mm | 235 |
DC U1mA kV | 8.11±0.40 |
Iref mA | 2 |
Uref kV | 5.82 |
Ures kV | 14.67±0.74 |
8/20uS repetitive charge transfer Qrs C | 0.4 |
2ms repetitive charge transfer Qrs C | 0.7 |
2ms duration of rectangular impulse current A | 350 |
4/10µs high current test kA | 100 |
Accelerated ageing test Kct | ≤ 1.0 |
Note:
The nouns, parameters and corresponding test methods in this parameter list conform to the standards of IEC60099-4:2014 and GB11032-2020.
The rated voltage, power frequency reference current and power frequency reference voltage are reference values.
The 2ms square wave tolerance value is based on the declared current/2ms repetitive charge transfer charge Qrs=423, if the actual test waveform 2ms current/2mS repetitive charge transfer charge Qrs is not equal to 423, it should be corrected according to the actual 2ms current waveform and Qrs value.
The charging rate of the aging test was 90%.
The number of pulses for the high current withstand value is two.
Type | D36H36.4 |
Nominal discharge current In kA | 10 |
Suggested rated voltage kV | 5.66 |
Diameter mm | 36±0.7 |
Height mm | 36.4±0.3 |
AVG Gradient V/mm | 235 |
DC U1mA kV | 8.55±0.45 |
Iref mA | 2 |
Uref kV | 6.14 |
Ures kV | 15.48±0.83 |
8/20uS repetitive charge transfer Qrs C | 0.4 |
2ms repetitive charge transfer Qrs C | 0.7 |
2ms duration of rectangular impulse current A | 350 |
4/10µs high current test kA | 100 |
Accelerated ageing test Kct | ≤ 1.0 |
Note:
The nouns, parameters and corresponding test methods in this parameter list conform to the standards of IEC60099-4:2014 and GB11032-2020.
The rated voltage, power frequency reference current and power frequency reference voltage are reference values.
The 2ms square wave tolerance value is based on the declared current/2ms repetitive charge transfer charge Qrs=423, if the actual test waveform 2ms current/2mS repetitive charge transfer charge Qrs is not equal to 423, it should be corrected according to the actual 2ms current waveform and Qrs value.
The charging rate of the aging test was 90%.
The number of pulses for the high current withstand value is two.
D36 Series MOV for Distribution Arrester provides a number of benefits. It provides superior protection against transient over-voltages, has a wide operating temperature range, and is extremely durable. It also has low power consumption, is reliable and cost-effective, and is easy to install and maintain. It also offers high surge current capability with a low voltage drop, and is designed to meet the latest industry standards for surge protection. In addition, it offers a long service life and has a high surge current capacity. As a renowned metal oxide varistor manufacturer, TGE is committed to delivering high-quality products like the D36 Series MOV for Distribution Arrester. Utilizing the zinc oxide varistor function, our MOV disc and ZOV MOV technologies provide exceptional surge protection, ensuring the longevity and reliability of your electrical systems.