D50 Series MOV Block for Substation Arrester

D50 Series MOV for Substation Arrester is a high-end product designed to protect 110-220kV heavy load surge arrester. It is made up of top-grade MOV varistor blocks of excellent performance, which can effectively absorb the transient current and effectively protect the arrester from overvoltage. It has the advantages of high current resistance, fast response, high reliability, and long service life. It is an ideal choice for protecting substation arrester from overvoltage hazards.

TGE Specification of D50H23.5 Metal Oxide Arrester Blocks


Type

D50H23.5

Nominal discharge current In kA

10

Suggested rated voltage kV

3.55

Diameter mm

50±1

Height mm

23.5±0.3

AVG Gradient V/mm

220

DC U1mA kV

5.17±0.30

Iref mA

3

Uref kV

3.62

Ures kV

8.84±0.52

8/20uS repetitive charge transfer Qrs C


2ms repetitive charge transfer Qrs C

1.5

2ms duration of rectangular impulse current A

800

4/10µs high current test kA

100

Accelerated ageing test Kct

≤ 1.0

Note:

  • The nouns, parameters and corresponding test methods in this parameter list conform to the standards of IEC60099-4:2014 and GB11032-2020.

  • The rated voltage, power frequency reference current and power frequency reference voltage are reference values.

  • The 2ms square wave tolerance value is based on the declared current/2ms repetitive charge transfer charge Qrs=423, if the actual test waveform 2ms current/2mS repetitive charge transfer charge Qrs is not equal to 423, it should be corrected according to the actual 2ms current waveform and Qrs value.

  • The charging rate of the aging test was 90%.

  • The number of pulses for the high current withstand value is two.




TGE Specification of D50H24 Metal Oxide Arrester Blocks


Type

D50H24

Nominal discharge current In kA

10

Suggested rated voltage kV

4.09

Diameter mm

50±1

Height mm

24±0.3

AVG Gradient V/mm

245

DC U1mA kV

5.93±0.30

Iref mA

3

Uref kV

4.15

Ures kV

10.14±0.52

8/20uS repetitive charge transfer Qrs C


2ms repetitive charge transfer Qrs C

1.5

2ms duration of rectangular impulse current A

800

4/10µs high current test kA

100

Accelerated ageing test Kct

≤ 1.0

Note:

  • The nouns, parameters and corresponding test methods in this parameter list conform to the standards of IEC60099-4:2014 and GB11032-2020.

  • The rated voltage, power frequency reference current and power frequency reference voltage are reference values.

  • The 2ms square wave tolerance value is based on the declared current/2ms repetitive charge transfer charge Qrs=423, if the actual test waveform 2ms current/2mS repetitive charge transfer charge Qrs is not equal to 423, it should be corrected according to the actual 2ms current waveform and Qrs value.

  • The charging rate of the aging test was 90%.

  • The number of pulses for the high current withstand value is two.




TGE Specification of D50H29 Metal Oxide Arrester Blocks


Type

D50H29

Nominal discharge current In kA

10

Suggested rated voltage kV

4.49

Diameter mm

50±1

Height mm

29±0.3

AVG Gradient V/mm

220

DC U1mA kV

6.41±0.30

Iref mA

3

Uref kV

4.57

Ures kV

10.96±0.61

8/20uS repetitive charge transfer Qrs C


2ms repetitive charge transfer Qrs C

1.5

2ms duration of rectangular impulse current A

800

4/10µs high current test kA

100

Accelerated ageing test Kct

≤ 1.0

Note:

  • The nouns, parameters and corresponding test methods in this parameter list conform to the standards of IEC60099-4:2014 and GB11032-2020.

  • The rated voltage, power frequency reference current and power frequency reference voltage are reference values.

  • The 2ms square wave tolerance value is based on the declared current/2ms repetitive charge transfer charge Qrs=423, if the actual test waveform 2ms current/2mS repetitive charge transfer charge Qrs is not equal to 423, it should be corrected according to the actual 2ms current waveform and Qrs value.

  • The charging rate of the aging test was 90%.

  • The number of pulses for the high current withstand value is two.




TGE Specification of D50H36 Metal Oxide Arrester Blocks


Type

D50H36

Nominal discharge current In kA

10

Suggested rated voltage kV

5.84

Diameter mm

50±1

Height mm

36±0.3

AVG Gradient V/mm

220

DC U1mA kV

7.88±0.35

Iref mA

3

Uref kV

5.92

Ures kV

13.47±0.70

8/20uS repetitive charge transfer Qrs C


2ms repetitive charge transfer Qrs C

1.5

2ms duration of rectangular impulse current A

800

4/10µs high current test kA

100

Accelerated ageing test Kct

≤ 1.0

Note:

  • The nouns, parameters and corresponding test methods in this parameter list conform to the standards of IEC60099-4:2014 and GB11032-2020.

  • The rated voltage, power frequency reference current and power frequency reference voltage are reference values.

  • The 2ms square wave tolerance value is based on the declared current/2ms repetitive charge transfer charge Qrs=423, if the actual test waveform 2ms current/2mS repetitive charge transfer charge Qrs is not equal to 423, it should be corrected according to the actual 2ms current waveform and Qrs value.

  • The charging rate of the aging test was 90%.

  • The number of pulses for the high current withstand value is two.




TGE Specification of D50H41 Metal Oxide Arrester Blocks


Type

D50H41

Nominal discharge current In kA

10

Suggested rated voltage kV

6.65

Diameter mm

50±1

Height mm

41±0.3

AVG Gradient V/mm

230

DC U1mA kV

9.40±0.45

Iref mA

3

Uref kV

6.75

Ures kV

16.07±0.78

8/20uS repetitive charge transfer Qrs C


2ms repetitive charge transfer Qrs C

1.5

2ms duration of rectangular impulse current A

800

4/10µs high current test kA

100

Accelerated ageing test Kct

≤ 1.0

Note:

  • The nouns, parameters and corresponding test methods in this parameter list conform to the standards of IEC60099-4:2014 and GB11032-2020.

  • The rated voltage, power frequency reference current and power frequency reference voltage are reference values.

  • The 2ms square wave tolerance value is based on the declared current/2ms repetitive charge transfer charge Qrs=423, if the actual test waveform 2ms current/2mS repetitive charge transfer charge Qrs is not equal to 423, it should be corrected according to the actual 2ms current waveform and Qrs value.

  • The charging rate of the aging test was 90%.

  • The number of pulses for the high current withstand value is two.




Benefits of D50 Series MOV for Substation Arrester


Benefits of D50 Series MOV for Substation Arrester


The D50 Series MOV for Substation Arrester is a reliable and cost-effective solution for heavy load surge protection in electrical substations. Featuring a durable MOV varistor block design, the D50 Series provides superior protection against extreme conditions and lightning-induced surges, helping to extend the lifespan of critical equipment and reduce downtime.  As a trusted metal oxide varistor manufacturer, we ensure that our D50 series MOV block for substation arrester incorporates the zinc oxide varistor function, providing robust protection against surges. Our mov disc is designed to withstand extreme conditions, offering superior surge protection for your critical substation equipment.

Products
Do you have any questions regarding MOV blocks or MOV disks?
Do you have any questions regarding MOV blocks or MOV disks?

Welcome to TGE's Customer Connect Center. Experienced specialists are here for you 365 days a year.

E-mail:
tge@xatge.com
Address:

No.53, Hong Guang Road, He Ping Industrial Park, San Qiao, Xi'an, China.

Get In Touch With TGE

Your Name *

Your Email *

Your Phone

Company

Your Message *

Related MOV Block for Substation Arrester

Latest News & Blogs about TGE
Smart Grid Solutions: How Distribution Arresters Enhance Electrical Infrastructure
18 Apr 2024

Smart Grid Solutions: How Distribution Arresters Enhance Electrical Infrastructure

How MOV Lightning Arresters Safeguard Your Electronics
08 Apr 2024

How MOV Lightning Arresters Safeguard Your Electronics

The Importance Of Regular Surge Arrester Testing
26 Mar 2024

The Importance Of Regular Surge Arrester Testing